PDMS
(PD Monitoring System)
On-Line 부분방전 모니터링 시스템
| Partial Discharge | PD Channel Quantity | 3 |
| Bandwidth | 16 kHz ~ 30 kHz | |
| Sampling Frequency | 100 MS/s | |
| Resolution | 10 bit | |
| Sensitivity | 1 ~ 4000 mVpp | |
| lnput Impedance | 50 fi | |
| Pre-Trigger | 0 ~ 100 % @ 10 µs | |
| 0 ~ 50 % @ 20 µs | ||
| 0 ~ 25 % @ 40 µs | ||
| Connector type | BNC |
| Synchronization Input | Channel Quantity | 1 |
| Frequency Range | 0.1 kHz ~ 1 kHz | |
| lnput Impedance | 10 Mfi | |
| Connector Type | NC | |
| Communication System | Fiber 0ptic | 2 ports |
| ST connectors | ||
| Power Supply | 5 VDC, 2 A | |
| Working Temperature Range | - 20 ºC ~ + 60 ºC | |